Parameters: 9-** Profibus - Danfoss FC 300 Series Programming Manual

Table of Contents

Advertisement

Parameter Descriptions

3.11 Parameters: 9-** Profibus

9-00 Setpoint
Range:
Function:
0
[0 - 65535 ] This parameter receives cyclical reference from a
*
Master Class 2. If the control priority is set to
Master Class 2, the reference for the adjustable
frequency drive is taken from this parameter,
whereas the cyclical reference will be ignored.
9-07 Actual Value
Range:
Function:
0
[0 - 65535 ] This parameter delivers the MAV for a Master
*
Class 2. The parameter is valid if the control
priority is set to Master Class 2.
9-15 PCD Write Configuration
Array [10]
Option:
[0]
None
*
[302]
Minimum Reference
[303]
Maximum Reference
[312]
Catch up/slow-down Value
[341]
Ramp 1 Ramp-up Time
[342]
Ramp 1 Ramp-down Time
[351]
Ramp 2 Ramp-up Time
[352]
Ramp 2 Ramp-down Time
[380]
Jog Ramp Time
[381]
Quick Stop Ramp Time
[411]
Motor Speed Low Limit [RPM]
[412]
Motor Speed Low Limit [Hz]
[413]
Motor Speed High Limit [RPM]
[414]
Motor Speed High Limit [Hz]
[416]
Torque Limit Motor Mode
[417]
Torque Limit Generator Mode
FC 300 Programming Guide
[590]
[593]
[595]
[597]
[653]
[663]
[673]
[683]
[748]
[890]
[891]
[1680] Fieldbus CTW 1
[1682] Fieldbus REF 1
[1685] FC Port CTW 1
[1686] FC Port REF 1
Function:
[3310] Synchronization Factor Master (M:S)
Select the
[3311] Synchronization Factor Slave (M:S)
parameters to be
[3401] PCD 1 Write to MCO
assigned to PCD 3 to
[3402] PCD 2 Write to MCO
10 of the messages.
[3403] PCD 3 Write to MCO
The number of
[3404] PCD 4 Write to MCO
available PCDs
[3405] PCD 5 Write to MCO
depends on the
[3406] PCD 6 Write to MCO
message type. The
[3407] PCD 7 Write to MCO
values in PCD 3 to 10
[3408] PCD 8 Write to MCO
will then be written
[3409] PCD 9 Write to MCO
to the selected
[3410] PCD 10 Write to MCO
parameters as data
values. Alternatively,
specify a standard
Profibus message in
9-22 Telegram
Selection.
[0]
[1472] VLT Alarm Word
[1473] VLT Warning Word
[1474] VLT Ext. Status Word
[1500] Operating Hours
[1501] Running Hours
[1502] kWh Counter
[1600] Control Word
®
MG.33.MA.22 - VLT
is a registered Danfoss trademark
9-15 PCD Write Configuration
Array [10]
Option:
Digital & Relay Bus Control
Pulse Out #27 Bus Control
Pulse Out #29 Bus Control
Pulse Out #X30/6 Bus Control
Terminal 42 Output Bus Control
Terminal X30/8 Bus Control
Terminal X45/1 Bus Control
Terminal X45/3 Bus Control
PCD Feed Forward
Bus Jog 1 Speed
Bus Jog 2 Speed
9-16 PCD Read Configuration
Array [10]
Option:
None
*
Function:
Function:
Select the parameters to be
assigned to PCD 3 to 10 of the
messages. The number of
available PCDs depends on
the message type. PCDs 3 to
10 contain the actual data
values of the selected
parameters. For standard
Profibus messages, see
9-22 Telegram Selection.
3-91
3
3