PID CONTROL APPLICATION
Table 36: Input signals, G2.2
Index
Parameter
I/O B reference
P2.2.5 **
selection
Keypad control
P2.2.6 **
reference selec-
tion
Fieldbus control
P2.2.7 **
reference selec-
tion
Actual value
P2.2.8 **
selection
Actual value 1
P2.2.9 **
selection
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/
Min
Max
Unit
0
7
0
7
0
7
0
7
0
10
Default
Cust
ID
1
343
4
121
5
122
0
333
2
334
VACON · 95
Description
0 = AI1
1 = AI2
2 = AI3
3 = AI4
4 = Keypad refer-
ence
5 = Fieldbus refer-
ence (FBSpeedRe-
ference)
6 = Motor potenti-
ometer
7 = PID controller
As in P2.2.5
As in P2.2.5
0 = Actual value 1
1 = Actual 1 +
Actual 2
2 = Actual 1 –
Actual 2
3 = Actual 1 *
Actual 2
4 = Min(Actual 1,
Actual 2)
5 = Max(Actual 1,
Actual 2)
6 = Mean(Actual1,
Actual2
7 = Sqrt (Act1) +
Sqrt (Act2)
0 = Not used
1 = AI1 signal (c-
board)
2 = AI2 signal (c-
board)
3 = AI3
4 = AI4
5 = Fieldbus Proc-
essDataIN2
6 = Motor torque
7 = Motor speed
8 = Motor current
9 = Motor power
10 = Encoder fre-
quency
5