VACON · 28
Table 7: Output signals, G2.3
Index
Parameter
Digital output 1
P2.3.7
function
P2.3.8
RO1 function
P2.3.9
RO2 function
Output frequency
P2.3.10
limit 1 supervision
Output frequency
P2.3.11
limit 1; Supervised
value
Analogue output 2
P2.3.12 *
signal selection
Analogue output 2
P2.3.13
function
Analogue output 2
P2.3.14
filter time
Analogue output 2
P2.3.15
inversion
Analogue output 2
P2.3.16
minimum
2
Min
Max
Unit
0
16
0
16
0
16
0
2
0.00
320.00
Hz
0.1
E.10
0
8
0.00
10.00
s
0
1
0
1
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/
STANDARD APPLICATION
Default
Cust
ID
1
312
2
313
3
314
0
315
0.00
316
0.1
471
4
472
1.00
473
0
474
0
475
Description
0 = Not used
1 = Ready
2 = Run
3 = Fault
4 = Fault inverted
5 = FC overheat
warning
6 = Ext. fault or
warning
7 = Ref. fault or
warning
8 = Warning
9 = Reversed
10 = Preset speed
1
11 = At speed
12 = Mot. regulator
active
13 = OP freq. limit
1 superv.
14 = Control place:
IO
15 = Therminstor
fault/warning
16 = Fieldbus DIN1
As parameter 2.3.7
As parameter 2.3.7
0 = No limit
1 = Low limit
supervision
2 = High limit
supervision
As parameter 2.3.2
0 = No filtering
0 = Not inverted
1 = Inverted
0 = 0 mA (0 V)
1 = 4 mA (2 V)

Advertisement