Vacon NX Series Applications Manual page 146

Ac drives
Hide thumbs Also See for NX Series:
Table of Contents

Advertisement

VACON · 146
Table 69: Drive control parameters, G2.4
Index
Parameter
Flux braking cur-
P2.4.13
rent
NXP drives only
DC-brake current
P2.4.14
at stop
Inching reference
P2.4.15
1
Inching reference
P2.4.16
2
P2.4.17
Inching ramp
Emergency stop
P2.4.18
mode
P2.4.19
Control options
P2.4.20
Modulator type
P2.4.21
Ramp; Skip S2
* = Parameter value can only be changed aftr the FC has been stopped.
6
Min
Max
Unit
0.00
I
A
L
0
I
A
L
-320.00
320.00
Hz
-320.00
320.00
Hz
0.1
3200.0
s
0
1
0
65536
0
1
0
1
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/
MULTI-PURPOSE CONTROL APPLICATION
Default
Cust
ID
I
519
H
0.1 x I
1080
H
2.00
1239
653.36
1240
1.0
1257
0
1276
0
1084
0
1516
0
1900
Description
0 = Coasting
1 = Ramp
0 = ASIC modulator
1 = Software Mod-
ulator 1

Advertisement

Table of Contents
loading