Table 184: Selections for parameter ID733
Selection
number
0
No Action
1
Warning
2
Fault
3
Fault, Coast
Warn:PresetF
4
(*) NXP drives, Multi-purpose application only.
734 RESPONSE TO SLOT FAULT 234567 (2.7.23)
Use this parameter to select the response of the drive to a 'Slot Communication' fault.
Set here the response mode for a board slot fault due to missing or broken board.
See parameter ID732.
738 AUTOMATIC RESTART: NUMBER OF TRIES AFTER UNDERLOAD FAULT TRIP (2.8.10)
Use this parameter to enable the automatic reset after an underload fault.
Table 185: Selections for parameter ID738
Selection
number
No automatic restart after
0
Underload fault trip
Number of automatic restarts
>0
after Underload fault trip
739 TBOARD1 NUMBERS (NUMBER OF PT100 INPUTS IN USE) 567 (2.7.24)
Use this parameter to select the number of sensors in use when a temperature board is
installed.
NOTE!
The parameter name TBoard1 Numbers is used in Multi-Purpose Control
Application. The old name (Number of PT100 inputs in use) is still used in PID
Control Application and Pump and Fan Control Application.
If you have a temperature board installed in your AC drive you can choose here the number
of sensors in use. See also the VACON
9
Selection name
No response
Warning
Fault, stop at fault according to parameter ID506
Fault, stop at fault always by coasting
Warning, frequency reference set to fieldbus fault preset fre-
quency (param. ID1801) (*)
Selection name
NX I/O Boards User Manual.
®
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/
PARAMETER DESCRIPTIONS
Description
Description