PARAMETER DESCRIPTIONS
100%
Par. ID349
Fig. 53: Reduction of torque supervision limit
363 START/STOP LOGIC SELECTION, PLACE B3 (2.2.15)
Use this parameter to control the start and stop of the drive with the digital signals.
Table 139: Selections for parameter ID363
Selection
DIN3
0
See Fig. 54.
1
See Fig. 55.
2
Can be programmed for
reverse command
3 *
See Fig. 56.
4 **
5 **
6 **
* = 3-wire connection (pulse control)
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/
Torque
limit
0
Signal range
DIN4
closed contact = start forward
closed contact = startopen
contact = stop
closed contact = start, open
contact = stop
closed contact= start pulse
closed contact = start forward
(Rising edge required to start)
closed contact = start (Rising
edge required to start)
open contact = stop
closed contact = start (Rising
edge required to start)
open contact = stop
Free
analogue
input
DIN5
closed contact = start reverse
closed contact = reverseopen
contact = forward
closed contact = start enabled,
open contact = start disabled and
drive stopped if running
open contact = stop pulse
closed contact = start reverse
(Rising edge required to start)
closed contact = reverse
open contact = forward
closed contact = start enabled
open contact = start disabled and
drive stopped if running
VACON · 255