VACON · 340
Table 202: Selections for parameter ID1089
Selection
number
Coasting, follower remains in
0
control even if master has
stopped at fault
Ramping, follower remains in
1
control even if master has
stopped at fault
As master; follower behaves as
2
master
1090 RESET ENCODER COUNTER 6 (2.2.7.29)
Use this parameter to select the digital input signal that resets the monitoring values Shaft
Angle and Shaft Rounds to zero.
See Table 44 Monitoring values, NXS drives.
The parameter is available for NXP drives only.
1092 MASTER FOLLOWER MODE 26 (2.2.7.31)
Use this parameter to select the digital input signal that activates the second Master
Follower mode.
Select the digital input to activate the second Master Follower mode selected by parameter
ID1093. The parameter is available for NXP drives only.
1093 MASTER FOLLOWER MODE 2 SELECTION 6 (2.11.7)
Use this parameter to select the Master Follower function.
Select Master Follower mode 2 that is used when the DI is activated. When Follower is
selected the Run Request command is monitored from Master and all other references are
selectable by parameters.
Table 203: Selections for parameter ID1093
Selection
number
0
Single Drive
1
Master
2
Follower
9
Selection name
Selection name
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/
PARAMETER DESCRIPTIONS
Description
Description