VACON · 268
Contact closed:Force control place to fieldbus
This input is preceded in priority by parameters ID409 and ID410.
NOTE!
When the control place is forced to change the values of Start/Stop, Direction and
Reference valid in the respective control place are used.
The value of parameter ID125 (Keypad Control Place) does not change.
When the input opens the control place is selected according to keypad control parameter
ID125.
412 REVERSE * 67 (2.2.7.4, 2.2.6.11)
Use this parameter to select the digital input signal that changes the direction when Start
signal 2 is used for other purposes.
Contact open: Direction forward
Contact closed: Direction reverse
This command is active when Start signal 2 (ID404) is used for other purposes.
413 JOGGING SPEED * 67 (2.2.7.16, 2.2.6.12)
Use this parameter to select the digital input signal that selects jogging speed for the
frequency reference.
Contact closed: Jogging speed selected for frequency reference
See parameter ID124.
Default programming: A.4.
414 FAULT RESET * 67 (2.2.7.10, 2.2.6.13)
Use this parameter to select the digital input signal that resets all active faults.
CLOSED = Resets all active faults.
415 ACCELERATION /DECELERATION PROHIBITED * 67 (2.2.7.14, 2.2.6.14)
Use this parameter to select the digital input signal that prevents the acceleration and the
deceleration of the drive.
No acceleration or deceleration is possible until the contact is open.
416 DC-BRAKING * 67 (2.2.7.15, 2.2.6.15)
Use this parameter to select the digital input signal that starts DC braking in the STOP mode.
Contact closed:In STOP mode, the DC braking operates until the contact is opened.
See ID1080.