PARAMETER DESCRIPTIONS
495 ADJUST MAXIMUM 6 (2.2.1.6)
Use this parameter to set additional scaling to the adjusted frequency reference.
See Fig. 66 An example of adjust input.
NOTE!
The adjustment is made to the basic reference signal.
496 PARAMETER SET 1/SET 2 SELECTION * 6 (2.2.7.21)
Use this parameter to set the digital input that selects the parameter set to be used.
This parameter defines the digital input, which can be used to select between Parameter Set
1 and Set 2. The input for this function can be selected from any slot. The procedure of
selecting between the sets is explained in the product's User Manual.
Digital input = FALSE:
Set 1 is loaded as the active set
-
Digital input = TRUE:
Set 2 is loaded as the active set
-
NOTE!
The parameter values are stored only when selecting P6.3.1 Parameter sets Store
Set 1 or Store Set 2 in System menu or from NCDrive: Drive > Parameter Sets.
498 START PULSE MEMORY 3 (2.2.24)
Use this parameter to select if the RUN status is copied when the control place is changed
between A and B.
Table 150: Selections for parameter ID498
Selection
Selection name
number
0
The RUN status is not copied
1
The RUN status is copied
In order for this parameter to have effect, parameters ID300 and ID363 must have been set
the value 3.
500 ACCELERATION/DECELARATION RAMP 1 SHAPE 234567 (2.4.1)
Use this parameter to make the start and the end of the acceleration and deceleration ramps
smoother.