PARAMETER DESCRIPTIONS
354 FREQUENCY CONVERTER TEMPERATURE LIMIT SUPERVISION 34567 (2.3.20, 2.3.4.11,
2.3.2.11)
Use this parameter to select the limit supervision function for the temperature of the AC
drive.
Table 135: Selections for parameter ID354
Selection
Selection name
number
0
No supervision
1
Low limit supervision
2
High limit supervision
If the temperature of the AC drive unit falls below or exceeds the set limit (ID355), this
function generates a message through a digital output depending on
1. the settings of parameters ID312 to ID314 (applications 3,4,5) or
2. to which output the temperature limit supervision signal (parameter ID450) is connected
(applications 6 and 7).
355 FREQUENCY CONVERTER TEMPERATURE LIMIT VALUE 34567 (2.3.21, 2.3.4.12, 2.3.2.12)
Use this parameter to set the limit supervision value for the temperature when you activate
the temperature limit supervision function.
This temperature value is supervised by parameter ID354.
356 ANALOGUE SUPERVISION SIGNAL 6 (2.3.4.13)
Use this parameter to select the analogue input you want to monitor.
Table 136: Selections for parameter ID356
Selection
Selection name
number
0
Not used
1
AI1
2
AI2
3
AI3
4
AI4
357 ANALOGUE SUPERVISION LOW LIMIT 6 (2.3.4.14)
Use this parameter to set the low limit for the analogue input you selected to be monitored.
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/
VACON · 251