VACON · 330
PARAMETER DESCRIPTIONS
1
1
M1
M2
Fig. 87: Autochange with all drives
1. Auxiliary connection
1029 AUTOCHANGE INTERVAL 7 (2.9.26)
Use this parameter to adjust the autochange intervals.
When this time is over, the autochange occurs if the capacity is below the level set with
parameters ID1031 (Autochange frequency limit) and ID1030 (Maximum number of auxiliary
drives). Should the capacity exceed the value of ID1031, the autochange will not take place
before the capacity goes below this limit.
The time count is activated only if the Start/Stop request is active.
The time count is reset after the autochange has taken place.
See Chapter 1031 Autochange frequency limit 7 (2.9.28).
1030 MAXIMUM NUMBER OF AUXILIARY DRIVES 7 (2.9.27)
Use this parameter to set the amount of auxiliary drives used.
1031 AUTOCHANGE FREQUENCY LIMIT 7 (2.9.28)
Use this parameter to set the autochange frequency limit.
These parameters define the level below which the capacity used must remain so that the
autochange can take place.
This level is defined as follows: