PARAMETER DESCRIPTIONS
Table 116: Selections for parameter ID301
Selection
Selection name
number
0
Not used
External fault
1
External fault
2
Run enable
3
Application 1
Run enable
4
Applications 2 to 5
Acc./Dec time
select.
4
5
Closing contact
6
Closing contact
Closing contact
7
Applications 2 to 5
Reverse
8
Applications 3 to 5
Jogging sp.
9
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/
Description
Closing contact: Fault is shown and respon-
ded to according to ID701.
Opening contact: Fault is shown and respon-
ded to according to ID701 when the input is
not active.
Contact open: Motor start disabled and the
motor is stopped
READY signal is set to FALSE
Contact closed: Motor start enabled
Contact open: Motor start enabled
Contact closed: Motor start disabled and the
motor is stopped
Contact open: Acceleration/deceleration time
1 selected
Contact closed: Acceleration/deceleration
time 2 selected
Force control place to I/O terminal
Force control place to keypad
Force control place to fieldbus
Contact open: Forward
Contact closed: Reverse
Contact closed: Jogging speed selected for
frequency reference
VACON · 227
Notes
When the control place is
forced to change the values
of Start/Stop, Direction and
Reference valid in the
respective control place are
used (reference according to
parameters ID117, ID121 and
ID122).
NOTE!
The value of parameter
ID125 Keypad Control Place
does not change.
When DIN3 opens the control
place is selected according
to parameter 3.1.
Can be used for reversing if
parameter ID300 value is set
to either 2,3, or 6.
9

Advertisement

Table of Contents
loading