VACON · 72
Table 26: Input signals, G2.2
Index
Parameter
AI2 custom set-
P2.2.11
ting minimum
AI2 custom set-
P2.2.12
ting maximum
AI2 signal inver-
P2.2.13
sion
AI2 signal filter
P2.2.14
time
Reference scaling
P2.2.15
minimum value
Reference scaling
P2.2.16
maximum value
Free analogue
P2.2.17
input, signal
selection
Free analogue
P2.2.18
input, function
CP = control place
cc = closing contact
oc = opening contact
** = Remember to place jumpers of block X2 accordingly. See the product's User Manual.
*** = Parameter value can only be changed after the AC drive has been stopped.
**** = Use TTF method to program these parameters.
4
Min
Max
Unit
-160.00
160.00
%
-160.00
160.00
%
0
1
0.00
10.00
s
0.00
320.00
Hz
0.00
320.00
Hz
0
2
0
4
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/
MULTI-STEP SPEED CONTROL APPLICATION
Default
Cust
ID
0.00
326
100.00
327
0
328
0.10
329
0.00
303
0.00
304
0
361
0
362
Description
0.00 = No scaling
>0 = scaled max.
value
0 = Not used
1 = AI1
2 = AI2
0 = No function
1 = Reduces current
limit (P2.1.5)
2 = Reduces DC
braking current,
P2.4.8
3 = Reduces accel.
and decel. tmes
4 = Reduces torque
supervision limit
P2.3.15