VACON · 252
358 ANALOGUE SUPERVISION HIGH LIMIT 6 (2.3.4.15)
Use this parameter to set the high limit for the analogue input you selected to be monitored.
These parameters set the low and high limits of the signal selected with parameter ID356.
AI *)
ID358
ID357
1
RO1
0
Fig. 49: An example of On/Off-control
*) Selected with par. ID356
NOTE!
In this example the programming of par. ID463 = B.1
359 PID CONTROLLER MINIMUM LIMIT 5 (2.2.30)
Use this parameter to set the minimum limit for the PID controller output.
360 PID CONTROLLER MAXIMUM LIMIT 5 (2.2.31)
Use this parameter to set the maximum limit for the PID controller output.
Limit setting: –1600.0% (of f
These limits are of importance for example when you define the gain, I-time and Dtime for
the PID controller.
361 FREE ANALOGUE INPUT, SIGNAL SELECTION 34 (2.2.20, 2.2.17)
Use this parameter to select the input signal for an analogue input that is not in use for
reference signal.
9
) < par. ID359 < par. ID360 < 1600.0% (of f
max