PARAMETER DESCRIPTIONS
Table 207: Selections for parameter ID1324
Selection
Selection name
number
0
Single Drive
1
Master
2
Follower
1352 SYSTEMBUS FAULT DELAY 6 (2.7.31)
Use this parameter to set the maximum time for which the heartbeat is missing before a
SystemBus fault occurs.
1355 TO 1369 FLUX 10-150% 6 (2.6.25.1 - 2.6.25.15)
Use this parameter to set the level of flux as a percentage of the nominal flux voltage.
Motor voltage corresponding to 10%-150% of flux as a percentage of nominal flux voltage.
1385 ID BIT FREE DO2 6 (P2.3.2.6)
Use this parameter to select the signal that controls the digital output.
The parameter has to be set in format xxxx.yy where xxxx is the ID number of a signal and yy
is the bit number. For example, the value for DO control is 43.06. 43 is the ID number of
Status Word. So the digital output is ON when bit number 06 of Status Word (ID no. 43) i.e.
Run Enable is on.
1401 STOP STATE FLUX 6 (2.6.23.24)
Use this parameter to set the flux that is kept in the motor after the AC drive stops.
The flux is maintained for the time set by parameter ID1402. This parameter can be used in
closed loop motor control mode only.
1402 FLUX OFF DELAY 6 (2.6.23.23)
Use this parameter to set the time for how long the Stop State Flux is kept in the motor after
the AC drive stops.
The flux defined by parameter ID1401 is maintained in the motor for the set time after the
drive is stopped. This function is used to shorten the time before the full motor torque is
available.
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/
VACON · 345
Description