481 ANALOGUE OUTPUT 3 INVERSION 67 (2.3.7.4, 2.3.5.4)
Use this parameter to invert the analogue output signal.
See ID309.
482 ANALOGUE OUTPUT 3 MINIMUM 67 (2.3.7.5, 2.3.5.5)
Use this parameter to set the minimum value of the analogue output signal.
Defines the signal minimum to either 0 mA or 4 mA (living zero). See ID310.
483 ANALOGUE OUTPUT 3 SCALING 67 (2.3.7.6, 2.3.5.6)
Use this parameter to set the scaling factor for the analogue output.
Value 200% will double the output. See ID311.
484 ANALOGUE OUTPUT 3 OFFSET 67 (2.3.7.7, 2.3.5.7)
Use this parameter to add offset to the analogue output.
Add –100.0 to 100.0% to the analogue output signal. See ID375.
485 SCALING OF MOTORING TORQUE LIMIT 6 (2.2.6.5)
Use this parameter to select the signal that adjusts the maximum motor torque limit.
Table 148: Selections for parameter ID485
Selection
number
0
Not used
1
AI1
2
AI2
3
AI3
4
AI4
5
Fieldbus (FBProcessDataIN2)
9
Selection name
See Chapter 9.7 Fieldbus control parameters (IDs 850 to 859)