Vacon NX Series Applications Manual page 157

Ac drives
Hide thumbs Also See for NX Series:
Table of Contents

Advertisement

MULTI-PURPOSE CONTROL APPLICATION
Table 78: Protections, G2.7
Index
Parameter
P2.7.14
Stall current
P2.7.15
Stall time limit
Stall frequency
P2.7.16
limit
Underload protec-
P2.7.17
tion
Field weakening
P2.7.18
area load
Zero frequency
P2.7.19
load
Underload protec-
P2.7.20
tion time limit
Response to ther-
P2.7.21
mistor fault
Response to field-
P2.7.22
bus fault
Response to slot
P2.7.23
fault
P2.7.24
TBoard1 Numbers
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/
Min
Max
Unit
0.00
P2.1.2
A
1.00
120.00
s
1.0
P2.1.2
Hz
0
3
10.0
150.0
%
5.0
150.0
%
2.00
600.00
s
0
3
0
4
0
3
0
5
Default
Cust
ID
1
710
H
15.00
711
25.0
712
0
713
50.0
714
10.0
715
20.00
716
2
732
2
733
2
734
0
739
VACON · 157
Description
0 = No response
1 = Warning
2 = Fault, stop acc.
to 2.4.7
3 = Fault, stop by
coasting
0 = No response
1 = Warning
2 = Fault, stop acc.
to 2.4.7
3 = Fault, stop by
coasting
0 = No response
1 = Warning
2 = Fault, stop acc.
to 2.4.7
3 = Fault, stop by
coasting
Warning, set freq.
ref. to fieldbus
fault preset fre-
quency (P2.7.40)
(NXP drives only)
See P2.7.21
0 = Not used
1 = Channel 1
2 = Channel 1 & 2
3 = Channel 1 & 2
& 3
4 = Channel 2 & 3
5 = Channel 3
6

Advertisement

Table of Contents
loading

Table of Contents