VACON · 260
Table 144: Selections for parameter ID372
Selection
number
0
Analogue input 1 (AI1)
1
Analogue input 2 (AI2)
373 ANALOGUE INPUT LIMIT SUPERVISION 7 (2.3.2.14)
Use this parameter select the limit supervision function for the selected analogue input.
If the value of the selected analogue input goes under/over the set supervision value
(parameter ID374) this function generates a message through the digital output or the relay
outputs depending on to which output the analogue input supervision function (parameter
ID463) is connected.
Table 145: Selections for parameter ID373
Selection
number
0
No supervision
1
Low limit supervision
2
High limit supervision
374 ANALOGUE INPUT SUPERVISED VALUE 7 (2.3.2.15)
Use this parameter to set the limit supervision value for the selected analogue input when
you activate the limit supervision function.
The value of the selected analogue input to be supervised by parameter ID373.
375 ANALOGUE OUTPUT OFFSET 67 (2.3.5.7, 2.3.3.7)
Use this parameter to add offset to the analogue output.
Add –100.0 to 100.0% to the analogue output signal.
376 PID SUM POINT REFERENCE (PLACE A DIRECT REFERENCE) 5 (2.2.4)
Use this parameter to select additional reference sources to the PID controller output when
PID controller is used.
9
Selection name
Selection name
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/
PARAMETER DESCRIPTIONS
Description
Description