PARAMETER DESCRIPTIONS
Table 182: Selections for parameter ID731
Selection
Selection name
number
0
Disabled
1
Enabled
The function resets the following faults (max. three times) (see the product's User Manual:
Overcurrent (F1)
•
Overvoltage (F2)
•
Undervoltage (F9)
•
Frequency converter overtemperature (F14)
•
Motor overtemperature (F16)
•
Reference fault (F50)
•
732 RESPONSE TO THERMISTOR FAULT 234567 (2.7.21)
Use this parameter to select the response of the drive to a 'Thermistor' fault.
Table 183: Selections for parameter ID732
Selection
Selection name
number
0
No response
1
Warning
Fault, stop mode after fault
2
according to ID506
Fault, stop mode after fault
3
always by coasting
Setting the parameter to 0 will deactivate the protection.
733 RESPONSE TO FIELDBUS FAULT 234567 (2.7.22)
Use this parameter to select the response of the drive to a 'Fieldbus Timeout' fault.
For more information, see the respective Fieldbus Board Manual.