PARAMETER DESCRIPTIONS
Table 182: Selections for parameter ID731
Selection
Selection name
number
0
Disabled
1
Enabled
The function resets the following faults (max. three times) (see the product's User Manual:
Overcurrent (F1)
Overvoltage (F2)
Undervoltage (F9)
Frequency converter overtemperature (F14)
Motor overtemperature (F16)
Reference fault (F50)
732 RESPONSE TO THERMISTOR FAULT 234567 (2.7.21)
Use this parameter to select the response of the drive to a 'Thermistor' fault.
Table 183: Selections for parameter ID732
Selection
Selection name
number
0
No response
1
Warning
Fault, stop mode after fault
2
according to ID506
Fault, stop mode after fault
3
always by coasting
Setting the parameter to 0 will deactivate the protection.
733 RESPONSE TO FIELDBUS FAULT 234567 (2.7.22)
Use this parameter to select the response of the drive to a 'Fieldbus Timeout' fault.
For more information, see the respective Fieldbus Board Manual.