Vacon NX Series Applications Manual page 36

Ac drives
Hide thumbs Also See for NX Series:
Table of Contents

Advertisement

VACON · 36
Table 11: Protections, G2.7
Index
Parameter
P2.7.14
Stall current
P2.7.15
Stall time limit
Stall frequency
P2.7.16
limit
Underload protec-
P2.7.17
tion
P2.7.18
UP From Torque
UP Zero fre-
P2.7.19
quency load
Underload protec-
P2.7.20
tion time limit
Response to ther-
P2.7.21
mistor fault
Response to field-
P2.7.22
bus fault
Response to slot
P2.7.23
fault
2
Min
Max
Unit
0.00
2 x I
A
H
1.00
120.00
s
1.0
P2.1.2
Hz
0
3
10.0
150.0
%
5.0
150.0
%
2.00
600.00
s
0
3
0
3
0
3
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/
STANDARD APPLICATION
Default
Cust
ID
I
710
H
15.00
711
25.00
712
0
713
50.0
714
10.0
715
20.00
716
2
732
2
733
2
734
Description
0 = No response
1 = Warning
2 = Fault, stop acc.
to 2.4.7
3 = Fault, stop by
coasting
0 = No response
1 = Warning
2 = Fault, stop acc.
to 2.4.7
3 = Fault, stop by
coasting
See P2.7.21
See P2.7.21