Vacon NX Series Applications Manual page 213

Ac drives
Hide thumbs Also See for NX Series:
Table of Contents

Advertisement

PARAMETER DESCRIPTIONS
122 FIELDBUS FREQUENCY REFERENCE SELECTION 234567 (2.1.13, 2.1.14, 2.2.7, 2.2.1.3)
Use this parameter to select the reference source when the control place is Fieldbus.
For selections in different applications, see ID121.
123 KEYPAD DIRECTION (3.3)
Use this parameter to set the rotation direction of the motor when the control place is
keypad.
Table 108: Selections for parameter ID123
Selection
Selection name
number
Forward
0
Reverse
1
For more information, see the product's User manual.
124 JOGGING SPEED REFERENCE 34567 (2.1.14, 2.1.15, 2.1.19)
Use this parameter to set the jogging frequency reference when the jogging speed function is
in use.
Defines the jogging speed reference when activated by digital input. See parameter ID301
and ID413.
The parameter value is automatically limited to Maximum frequency (ID102).
125 CONTROL PLACE (3.1)
Use this parameter to select the control place.
For more information, see the product's User manual.
Pushing the Start button for 3 seconds selects the control keypad as the active control place
and copies the Run status information (Run/Stop, direction and reference).
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/
Description
The rotation of the motor is forward, when the keypad is the
active control place.
The rotation of the motor is reversed, when the keypad is the
active control place.
VACON · 213
9

Advertisement