Vacon NX Series Applications Manual page 318

Ac drives
Hide thumbs Also See for NX Series:
Table of Contents

Advertisement

VACON · 318
With this parameter it is possible to select whether the activated safe disable function is
responded as fault or warning. The safe disable input will stop the drive modulation
regardless of this parameter value.
756 SAFE DISABLE ACTIVE 6 (2.3.3.30)
Use this parameter to select the digital output signal that shows the status of the Safe
Disable.
776 RESPONSE TO ACTIVE FILTER FAULT 6 (2.7.41)
Use this parameter to set the fault response for the active filter fault.
This parameters defines the response to be triggered when the active filter fault input (set
with param. ID214) is closed.
Table 190: Selections for parameter ID776
Selection
number
0
No Action
1
Warning
2
Fault
3
Fault, Coast
This parameter is present in NXP drives only.
850 FIELDBUS REFERENCE MINIMUM SCALING 6 (2.9.1)
Use this parameter to set scaling to the fieldbus reference signal.
851 FIELDBUS REFERENCE MAXIMUM SCALING 6 (2.9.2)
Use this parameter to set scaling to the fieldbus reference signal.
If ID850 = ID851 custom scaling is not used and the minimum and maximum fre quencies are
used for scaling.
The scaling takes place as presented in . See also Chapter 9.7 Fieldbus control parameters
(IDs 850 to 859).
NOTE!
Using this custom scaling function also affects the scaling of the actual value.
852 TO 859 FIELDBUS DATA OUT SELECTIONS 1 TO 8 6 (2.9.3 TO 2.9.10)
Use this parameter to select the data that is sent to the fieldbus with the ID number of the
parameter or monitor value.
9
Selection name
No response
Warning
Fault, stop at fault according to parameter ID506
Fault, stop at fault always by coasting
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/
PARAMETER DESCRIPTIONS
Description