Vacon NX Series Applications Manual page 228

Ac drives
Hide thumbs Also See for NX Series:
Table of Contents

Advertisement

VACON · 228
Table 116: Selections for parameter ID301
Selection
Selection name
number
10
Fault reset
Acc./dec. operation
11
prohibited
DC-braking com-
mand
12
Applications 3 and 5
Motor potentiome-
13
ter down
Application 4
13
Preset speed
f
out
DIN3
RUN
STOP
Fig. 33: DIN3 as DC-brake command input
A. Stop mode = Ramp
302 ANALOGUE INPUT 2, REFERENCE OFFSET 12 (2.15, 2.2.3)
Use this parameter to set the reference offset for analogue input.
Table 117: Selections for parameter ID302
Selection
number
0
No offset: 0—20 mA
Offset 4 mA ("living zero")
1
9
Description
Contact closed: Resets all faults
Contact closed: Stops acceleration or decel-
eration until the contact is opened
Contact closed: In Stop mode, the DC-braking
operates until the contact is opened, see Fig-
ure 30 as well as parameters ID507 and
ID1080
Contact closed: Reference decreases until the
contact is opened
A
ID515
t
Selection name
Provides supervision of zero level signal. In Standard Appli-
cation, the response to reference fault can be programmed
with parameter ID700.
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/
f
B
out
DIN3
RUN
STOP
B. Stop mode = coasting
Description
PARAMETER DESCRIPTIONS
Notes
t