PARAMETER DESCRIPTIONS
If you wish to make the Stop button a "hotspot" which always stops the drive regardless of
the selected control place, give this parameter the value 1.
See also parameter ID125.
117 I/O FREQUENCY REFERENCE SELECTION 12346 (2.14, 2.1.11)
Use this parameter to select the reference source when the control place is I/O A.
Table 106: Selections for parameter ID117
Applic.
Sel.
0
Analogue input 1 (AI1)
1
Anlogue input 2 (AI2).
2
Keypad reference (Menu M3)
3
Fieldbus reference
Potentiometer reference (Application 3
4
only)
5
6
7
8
9
10
11
12
13
14
15
16
118 PID CONTROLLER GAIN 57 (2.1.12)
Use this parameter to adjust the gain of the PID controller.
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/
1 to 4
Analogue input 1 (AI1). See ID377
Anlogue input 2 (AI2). See ID388
AI1+AI2
AI1–AI2
AI2–AI1
AI1*AI2
AI1 joystick
AI2 joystick
Keypad reference (Menu M3)
Fieldbus reference
Potentiometer reference; controlled with ID418
(TRUE=increase) and ID417 (TRUE=decrease)
AI1 or AI2, whichever is lower
AI1 or AI2, whichever is greater
Max. frequency (recommended in torque control
only)
AI1/AI2 selection, see ID422
Encoder 1 (AI input C.1)
Encoder 2 (With OPTA7 Speed Synchronization,
NXP only) (AI input C.3)