417 MOTOR POTENTIOMETER DOWN * 67 (2.2.7.8, 2.2.6.16)
Use this parameter to decrease the output frequency with a digital input signal.
Contact closed: Motor potentiometer reference DECREASES until the contact is opened.
418 MOTOR POTENTIOMETER UP * 67 (2.2.7.9, 2.2.6.17)
Use this parameter to increase the output frequency with a digital input signal.
Contact closed:Motor potentiometer reference INCREASES until the contact is opened.
419 PRESET SPEED * 16 (2.2.7.5)
Use this parameter to select the digital input signal that is used as a selector for the preset
frequencies.
420 PRESET SPEED * 26 (2.2.7.6)
Use this parameter to select the digital input signal that is used as a selector for the preset
frequencies.
421 PRESET SPEED * 36 (2.2.7.7)
Use this parameter to select the digital input signal that is used as a selector for the preset
frequencies.
422 AI1/AI2 SELECTION * 6 (2.2.7.17)
Use this parameter to select the analogue input signal that is used for the frequency
reference.
With value 14 selected for parameter ID117, this parameter allows you to select either AI1 or
AI2 signal for the frequency reference.
423 START A SIGNAL * 7 (2.2.6.1)
Use this parameter to select the digital input signal that starts and stops the drive when the
control place is I/O A.
Default programming: A.1
424 START B SIGNAL * 7 (2.2.6.2)
Use this parameter to select the digital input signal that starts and stops the drive when the
control place is I/O B.
Default programming: A.4
425 CONTROL PLACE A/B SELECTION * 7 (2.2.6.3)
Use this parameter to select the digital input signal that selects the control place I/O A or I/O
B.