VACON · 222
167 PID REFERENCE 1 57 (3.4)
Use this parameter to set the reference value of the PID controller.
The PID controller keypad reference can be set between 0% and 100%. This reference value
is the active PID reference if parameter ID332 = 2.
168 PID REFERENCE 2 57 (3.5)
Use this parameter to set the reference value of the PID controller.
The PID controller keypad reference 2 can be set between 0% and 100%. This reference is
active if the DIN5 function = 13 and the DIN5 contact is closed.
169 FIELDBUS DIN4 (FBFIXEDCONTROLWORDK, BIT 6) 6 (2.3.3.27)
Use this parameter to connect the Fieldbus signal (FBFixedControlWord) to the digital input
of your choice.
170 FIELDBUS DIN 5 (FBFIXEDCONTROLWORD, BIT 7) 6 (2.3.3.28)
Use this parameter to connect the Fieldbus signal (FBFixedControlWord) to the digital input
of your choice.
See the used fieldbus manual for more details.
179 SCALING OF MOTORING POWER LIMIT 6 (2.2.6.7)
Use this parameter to set limit to the maximum motor power.
The motoring power limit is equal to ID1289 if value 0 'Not used' is selected. If any of the
inputs is selected the motoring power limit is scaled between zero and parameter ID1289.
This parameter is available for NXP closed loop control mode only.
Table 114: Selections for parameter ID179
Selection
number
0
Not used
1
AI1
2
AI2
3
AI3
4
AI4
FB Limit Scaling ID46 (monitor-
5
ing value)
214 ACTIVE FILTER FAULT INPUT 6 (2.2.6.7)
Use this parameter to enable Active Filter Fault.
9
Selection name
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/
PARAMETER DESCRIPTIONS