PARAMETER DESCRIPTIONS
VACON · 267
405 EXTERNAL FAULT (CLOSE) * 67 (2.2.7.11, 2.2.6.4)
Use this parameter to select the digital input signal that activates an external fault.
Contact closed:Fault (F51) is displayed and motor stopped.
406 EXTERNAL FAULT (OPEN) * 67 (2.2.7.12, 2.2.6.5)
Use this parameter to select the digital input signal that activates an external fault.
Contact open:Fault (F51) is displayed and motor stopped.
407 RUN ENABLE * 67 (2.2.7.3, 2.2.6.6)
Use this parameter to select the digital input signal that sets the drive to Ready state.
When the contact is OPEN, the start of the motor is disabled.
When the contact is CLOSED, the start of the motor is enabled.
To stop, the drive obeys the value of parameter ID506. The follower drive will always coast to
stop.
408 ACCELERATION/DECELERATION TIME SELECTION * 67 (2.2.7.13, 2.2.6.7)
Use this parameter to select the digital input signal that selects the acceleration/
deceleration time 1 or 2.
When the contact is OPEN, the Acceleration/Deceleration time 1 selected
When the contact is CLOSED, the Acceleration/Deceleration time 2 selected
Set Acceleration/Deceleration times with parameters ID103 and ID104 and the alternative
ramp times with ID502 and ID503.
409 CONTROL FROM I/O TERMINAL * 67 (2.2.7.18, 2.2.6.8)
Use this parameter to select the digital input signal that switches the control place and the
frequency reference source to I/O terminal (from any control place).
Contact closed:Force control place to I/O terminal
This input has priority over parameters ID410 and ID411.
410 CONTROL FROM KEYPAD * 67 (2.2.7.19, 2.2.6.9)
Use this parameter to select the digital input signal that switches the control place and the
frequency reference source to Keypad (from any control place).
Contact closed:Force control place to keypad
This input has priority over parameter ID411 but preceded in priority by ID409.
411 CONTROL FROM FIELDBUS * 67 (2.2.7.20, 2.2.6.10)
Use this parameter to select the digital input signal that switches the control place and the
frequency reference source to Fieldbus (from I/O A, I/O B or Local control).
9
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/