PARAMETER DESCRIPTIONS
VACON · 271
433 RUN * 67 (2.3.3.2, 2.3.1.2)
Use this parameter to select a digital output for the run status.
434 FAULT * 67 (2.3.3.3, 2.3.1.3)
Use this parameter to select a digital output for the fault status.
435 INVERTED FAULT * 67 (2.3.3.4, 2.3.1.4)
Use this parameter to select a digital output for the fault inverted status.
436 WARNING * 67 (2.3.3.5, 2.3.1.5)
Use this parameter to select a digital output for the warning status.
437 EXTERNAL FAULT OR WARNING * 67 (2.3.3.6, 2.3.1.6)
Use this parameter to select a digital output for the external fault status.
Fault or warning depending on parameter ID701.
438 REFERENCE FAULT OR WARNING * 67 (2.3.3.7, 2.3.1.7)
Use this parameter to select a digital output for the AI reference fault status.
Fault or warning depending on parameter ID700.
439 DRIVE OVERTEMPERATURE WARNING * 67 (2.3.3.8, 2.3.1.8)
Use this parameter to select a digital output for the over temperature fault status.
The heatsink temperature exceeds the warning limit.
440 REVERSE * 67 (2.3.3.9, 2.3.1.9)
Use this parameter to select a digital output for the reverse status.
441 UNREQUESTED DIRECTION * 67 (2.3.3.10, 2.3.1.10)
Use this parameter to select a digital output for the direction difference status.
Motor rotation direction is different from the requested one.
442 AT SPEED * 67 (2.3.3.11, 2.3.1.11)
Use this parameter to select a digital output for the motor running at reference speed status.
The output frequency has reached the set reference.
Hysteresis is equal to motor nominal slip with induction motors and to 1.00 Hz with PMS
motors.
443 JOGGING SPEED * 67 (2.3.3.12, 2.3.1.12)
Use this parameter to select a digital output for the jogging speed status.
9