PARAMETER DESCRIPTIONS
723 AUTOMATIC RESTART: NUMBER OF TRIES AFTER 4MA REFERENCE TRIP 234567 (2.8.7)
Use this parameter to set how many automatic restarts the AC drive can make during the set
trial time after a 4mA fault.
Table 177: Selections for parameter ID 723
Selection
Selection name
number
No automatic restart after ref-
0
erence fault trip
Number of automatic restarts
after the analogue current sig-
>0
nal (4-20mA) has returned to
the normal level (>4mA)
725 AUTOMATIC RESTART: NUMBER OF TRIES AFTER EXTERNAL FAULT TRIP 234567 (2.8.9)
Use this parameter to set how many automatic restarts the AC drive can make during the set
trial time after an external fault.
Table 178: Selections for parameter ID725
Selection
Selection name
number
No automatic restart after
0
External fault trip
Number of automatic restarts
>0
after External fault trip
726 AUTOMATIC RESTART: NUMBER OF TRIES AFTER MOTOR TEMPERATURE FAULT TRIP
234567 (2.8.8)
Use this parameter to set how many automatic restarts the AC drive can make during the set
trial time after a motor temperature fault.
Table 179: Selections for parameter ID726
Selection
Selection name
number
No automatic restart after
0
Motor temperature fault trip
Number of automatic restarts
>0
after the motor temperature
has returned to its normal level
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/