Vacon NX Series Applications Manual page 325

Ac drives
Hide thumbs Also See for NX Series:
Table of Contents

Advertisement

PARAMETER DESCRIPTIONS
Table 192: Selectable wake-up functions
Selection
Function
number
Wake up happens
when actual value
goes below the
limit
2
Wake up happens
when actual value
exceeds the limit
3
1020 PID CONTROLLER BYPASS 7 (2.9.16)
Use this parameter to select if the PID controller is bypassed.
Then the frequency of the controlled drive and the starting points of the auxiliary drives are
defined according to the actual value signal.
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/
Limit
The limit defined with
parameter ID1018 is in
percent of the current
value of the reference sig-
nal
The limit defined with
parameter ID1018 is in
percent of the current
value of the reference sig-
nal
Description
Actual
value
signal
100%
reference=50%
Par. ID1018=60%
limit=60%*reference=30%
Start
Stop
Actual
value
signal
100%
Par. ID1018=140%
limit=140%*reference=70%
reference=50%
VACON · 325
t
t
Start
Stop
9

Advertisement

Table of Contents
loading

Table of Contents