PARAMETER DESCRIPTIONS
Table 146: Selections for parameter ID376
Selection
Selection name
number
0
No additional reference
PID output + AI1 reference from
1
terminals 2 and 3 (e.g. potenti-
ometer)
PID output + AI2 reference from
2
terminals 4 and 5 (e.g. trans-
ducer)
PID output + PID keypad refer-
3
ence
PID output + Fieldbus reference
4
(FBSpeedReference)
PID output + Motor potentiome-
5
ter reference
PID output + Fieldbus + PID
6
output (ProcessDataIN3)
PID output + Motor potentiome-
7
ter
If value 7 is selected for this parameter, the values of parameters ID319 and ID301 are
automatically set to 13.
Hz
30.00
20.00
Fig. 57: PID sum point reference
NOTE!
The maximum and minimum limits illustrated in the picture limit only the PID
output, no other outputs.
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/
(Direct PID output value)
see Chapter 9.7 Fieldbus control parameters (IDs 850 to 859)
PID Max limit
PID Min limit
VACON · 261
Description