VACON · 286
Fig. 70: Example of prohibit frequency area setting
515 DC BRAKING FREQUENCY AT STOP 234567 (2.4.10)
Use this parameter to set the output frequency at which the DC braking starts.
See Fig. 70 Example of prohibit frequency area setting.
516 DC-BRAKING TIME AT START 234567 (2.4.11)
Use this parameter to set the time during which the DC current is fed to the motor before the
acceleration starts.
DC brake current is used at start in order to premagnetize the motor before running. This
will improve the torque performance at start. Varying between 100 ms to 3 s, the time
needed depends on motor size. A bigger motor requires a longer time. See parameter ID507.
NOTE!
When Flying Start (see parameter ID505) is used as start function DC braking at
start is disabled.
518 ACCELERATION/DECELERATION RAMP SPEED SCALING RATIO BETWEEN PROHIBIT
FREQUENCY LIMITS 23457 (2.5.3, 2.5.7)
Use this parameter to set the multiplier of the selected ramp times when the output
frequency of the drive is between the prohibited frequency limits.
Defines the acceleration/deceleration time when the output frequency is between the
selected prohibit frequency range limits (parameters ID509 to ID514). The ramping speed
(selected acceleration/ deceleration time 1 or 2) is multiplied with this factor. E.g. value 0.1
makes the acceleration time 10 times shorter than outside the prohibit frequency range
limits.
9
Actual Reference
High Lim
Low Lim
ID509
ID511
ID513
Low
Lim
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/
PARAMETER DESCRIPTIONS
ID510
ID512
ID514
High
Requested
Lim
Reference