Vacon NX Series Applications Manual page 372

Ac drives
Hide thumbs Also See for NX Series:
Table of Contents

Advertisement

VACON · 372
Fault
Fault
code
7
Saturation trip
8
System fault
10
Subcode in
Possible cause
T.14
defective component
brake resistor short-
circuit or overload
S1 =
Reserved
operation malfunction
defective component
S2 =
Reserved
S3 =
Reserved
S4 =
Reserved
S5 =
Reserved
S6 =
Reserved
S7 =
Charging
switch
S8 = No
power to
driver card
S9 = Power
unit com-
munication
(TX)
S10 =
Power unit
communi-
cation
(Trip)
S11 =
Power unit
comm.
(Measure-
ment)
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/
FAULT TRACING
How to correct the fault
This fault cannot be reset from the
control panel.
Switch off the power.
DO NOT RESTART THE DRIVE or
CONNECT THE POWER!
Ask instructions from the factory.
If this fault shows at the same time
with Fault 1, do a check of the
motor cable and the motor.
Reset the fault and start the drive
again.
If the fault shows again, ask
instructions from the distributor
near to you.