PARAMETER DESCRIPTIONS
303 REFERENCE SCALING, MINIMUM VALUE 2346 (2.2.4, 2.2.16, 2.2.2.6)
Use this parameter to set additional reference scaling.
304 REFERENCE SCALING, MAXIMUM VALUE 2346 (2.2.5, 2.2.17, 2.2.2.7)
Use this parameter to set additional reference scaling.
If both parameter ID303 and parameter ID304 = 0 scaling is set off. The minimum and
maximum frequencies are used for scaling.
NOTE!
This scaling does not affect the fieldbus reference (scaled between Minimum
frequency (parameter ID101) and Maximum frequency (parameter ID102).
f
out
f
ID102
max
ID304
ID303
f
ID101
min
0
Fig. 34: Left: Reference scaling; Right: No scaling used (parameter ID303 = 0)
305 REFERENCE INVERSION 2 (2.2.6)
Use this parameter to invert the reference direction.
Inverts reference signal:
Max. input signal = Min. freq. reference
Min. input signal = Max. freq. reference
Table 118: Selections for parameter ID305
Selection
Selection name
number
0
No inversion
1
Reference inverted
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/
f
out
f
ID102
max
AI [V]
f
ID101
min
10
0
VACON · 229
AI [V]
10
Description