Table 199: Selections for parameter ID1084
Selection
number
b0
Disables encoder fault
Update Ramp Generator when
b1
MotorControlMode changes
from TC (4) to SC (3)
RampUp; use acceleration
b2
ramp (for Closed Loop torque
control)
RampDown; use deceleration
b3
ramp (for Closed Loop torque
control)
FollowActual; follow actual
speed value within WindowPos/
b4
NegWidth (for closed loop tor-
que control)
TC ForceRampStop; Under stop
b5
request the speed limit forces
the motor to stop
b6
Reserved
Disables switching frequency
b7
decrease
Disable the parameter "Run
b8
state parameter lock"
b9
Reserved
b10
Invert delayed digital output 1
b11
Invert delayed digital output 2
1085 BRAKE ON/OFF CURRENT LIMIT 6 (2.3.4.16)
Use this parameter to set the brake current limit.
The mechanical brake closes immediately if the motor current is below this value.
This parameter is available for NXP drives only.
1087 SCALING OF GENERATING TORQUE LIMIT 6 (2.2.6.6)
Use this parameter to select the analogue input signal that adjusts the maximum motor
generating torque.
9
Selection name
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/
PARAMETER DESCRIPTIONS