Fig. 90: Ramp; Skip S2
Second S curve is bypassed when reference changes at 25 Hz.
9.1

KEYPAD CONTROL PARAMETERS

Unlike the parameters listed above, these parameters are located in the M3 menu of the
control keypad. The frequency and torque reference parameters do not have an ID number.
114 STOP BUTTON ACTIVATED (3.4, 3.6)
Use this parameter to enable the keypad stop button.
If you wish to make the Stop button a "hotspot" which always stops the drive regardless of
the selected control place, give this parameter the value 1.
See also parameter ID125.
125 CONTROL PLACE (3.1)
Use this parameter to select the control place.
The active control place can be changed with this parameter. For more information, see the
product's User Manual.
Pushing the Start button for 3 seconds selects the control keypad as the active control place
and copies the Run status information (Run/Stop, direction and reference).