VACON · 220
Table 112: Selection for parameter ID143
Applic.
Sel.
0
1
4 mA/20-100%
2
3
144 AI3 CUSTOM SETTING MINIMUM 67 (2.2.4.4)
Use this parameter to adjust the scaling of the analogue input signal between -160%...160%
freely.
145 AI3 CUSTOM SETTING MAXIMUM 67 (2.2.4.5)
Use this parameter to adjust the scaling of the analogue input signal between -160%...160%
freely.
Set the custom minimum and maximum levels for the AI3 signal within - 160...160%.
Example: Min 40%, Max 80% = 8-16 mA.
151 AI3 SIGNAL INVERSION 567 (2.2.40, 2.2.4.6)
Use this parameter to invert the analogue input signal.
Table 113: Selections for parameter ID151
Selection
number
0
No inversion
1
Signal inverted
152 AI4 SIGNAL SELECTION * 567 (2.2.42, 2.2.5.1)
Use this parameter to connect the AI signal to the analogue input of your choice.
See ID141.
153 AI4 FILTER TIME 567 (2.2.45, 2.2.5.2)
Use this parameter to filter out disturbances in the analogue input signal.
See ID142.
9
5
0-100%
Selection name
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/
6
0-100%
4 mA/20-100%
–10...+10V
Customised
Description
PARAMETER DESCRIPTIONS
7
0-100%
4 mA/20-100%
Customised