VACON · 214
Table 109: Selections for parameter ID125
Selection
number
PC Control, (activated by
0
NCDrive)
1
I/O terminal
2
Keypad
3
Fieldbus
126 PRESET SPEED 3 46 (2.1.17)
Use this parameter to set the preset speed reference when the preset speed function is
used.
127 PRESET SPEED 4 46 (2.1.18)
Use this parameter to set the preset speed reference when the preset speed function is
used.
128 PRESET SPEED 5 46 (2.1.19)
Use this parameter to set the preset speed reference when the preset speed function is
used.
129 PRESET SPEED 6 46 (2.1.20)
Use this parameter to set the preset speed reference when the preset speed function is
used.
130 PRESET SPEED 7 46 (2.1.21)
Use this parameter to set the preset speed reference when the preset speed function is
used.
These parameters can be used to determine frequency references that are applied when
appropriate combinations of digital inputs are activated.
In Multi-Step Speed Application (Application 4), digital inputs DIN4, DIN5 and DIN6 are
assigned to Preset Speed functions. The combinations of these activated inputs select the
preset speed reference.
NOTE!
The use of TTF-programming method in the Multi-purpose Control Application.
Because all digital inputs are programmable you first have to assign three DINs for
the Preset Speed functions (parameters ID41, ID420 and ID421.