FAULT TRACING

10
FAULT TRACING
10.1

FAULT CODES

Fault
Fault
code
1
Overcurrent
2
Overvoltage
3 *
Earth fault
5
Charging switch
6
Emergency stop
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/
Subcode in
Possible cause
T.14
S1 = Hard-
There is too high a current
ware trip
(>4*I H) in the motor cable.
Its cause can be 1 of these.
S2 =
Reserved
a sudden heavy load
increase
S3 = Cur-
a short circuit in the
rent con-
motor cables
troller
the motor is not the
supervision
correct type
S4 = User
configured
overcur-
rent limit
exceeded
S1 = Hard-
The DC-link voltage is
ware trip
higher than the limits.
S2 = Over-
too short a decelera-
voltage
tion time
control
high overvoltage spikes
supervision
in the supply
Start/Stop sequence
too fast
The measurement of cur-
rent tells that the sum of the
motor phase current is not
zero.
an insulation malfunc-
tion in the cables or the
motor
The charging switch is open,
when the START command
is given.
operation malfunction
defective component
Stop signal has been given
from the option board.
VACON · 371
How to correct the fault
Do a check of the loading.
Do a check of the motor.
Do a check of the cables and con-
nections.
Make an identification run.
Set the deceleration time longer.
Use the brake chopper or the brake
resistor. They are available as
options.
Activate the overvoltage controller.
Do a check of the input voltage.
Do a check of the motor cables and
the motor.
Reset the fault and start the drive
again.
If the fault shows again, ask
instructions from the distributor
near to you.
Do a check of the emergency stop
circuit.