VACON · 352
Table 211: Selections for parameter ID125
Selection
number
PC Control, Activated by
0
NCDrive
1
I/O terminal
2
Keypad
3
Fieldbus
123 KEYPAD DIRECTION (3.3)
Use this parameter to set the rotation direction of the motor when the control place is
keypad.
Table 212: Selections for parameter ID123
Selection
number
Forward
0
Reverse
1
For more information, see the product's User Manual.
R3.2 KEYPAD REFERENCE (3.2)
The frequency reference can be adjusted from the keypad with this parameter.
The output frequency can be copied as the keypad reference by pushing the Stop button for 3
seconds when you are on any of the pages of menu M3. For more information, see the
product's User Manual.
167 PID REFERENCE 1 57 (3.4)
Use this parameter to set the reference value of the PID controller.
The PID controller keypad reference can be set between 0% and 100%. This reference value
is the active PID reference if parameter ID332 = 2.
168 PID REFERENCE 2 57 (3.5)
Use this parameter to set the reference value of the PID controller.
The PID controller keypad reference 2 can be set between 0% and 100%. This reference is
active if the DIN5 function = 13 and the DIN5 contact is closed.
9
Selection name
Selection name
The rotation of the motor is forward, when the keypad is the
active control place.
The rotation of the motor is reversed, when the keypad is the
active control place.