LOCAL/REMOTE CONTROL APPLICATION
Table 16: Input signals, G2.2
Index
Parameter
P2.2.2
DIN3 function
P2.2.3
AI1 signal selec-
****
tion
P2.2.4
AI1 signal range
AI1 custom set-
P2.2.5
ting minimum
AI1 custom set-
P2.2.6
ting maximum
AI1 signal inver-
P2.2.7
sion
AI1 signal filter
P2.2.8
time
P2.2.9
AI2 signal selec-
****
tion
P2.2.10
AI2 signal range
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/
Min
Max
Unit
0
13
0.1
E.10
0
2
-160.00
160.00
%
-160.00
160.00
%
0
1
0.00
10.00
s
0.1
E.10
0
2
Default
Cust
ID
1
301
A1
377
0
320
0.00
321
100.00
322
0
323
0.10
324
A.2
388
1
325
VACON · 47
Description
0 = Not used
1 = Ext. fault, closing
cont.
2 = Ext. fault, open-
ing cont.
3 = Run enable
4 = Acc./Dec. time
select.
5 = Force cp. to IO
6 = Force cp. to key-
pad
7 = Force cp. to field-
bus
8 = Reverse
9 = Jogging speed
11 = Acc./Dec. oper-
ation prohibit
12 = DC Braking
command
13 = Motor potenti-
ometer DOWN
0 = 0-10V (0-20
mA**)
1 = 2-10V (4-20
mA**)
2 = Custom setting
range**
0 = 0-10V (0-20
mA**)
1 = 2-10V (4-20
mA**)
2 = Custom setting
range**
3