PARAMETER DESCRIPTIONS
Table 204: Selections for parameter ID1276
Selection
Selection name
number
0
Coasting stop
1
Ramping stop
1278 TORQUE SPEED LIMIT, CLOSED LOOP 6 (2.10.6)
Use this parameter to select the output frequency limit mode for the torque control.
Table 205: Selections for parameter ID1278
Selection
Selection name
number
0
Closed Loop speed control
Positive and negative frequency
1
limit
2
Ramp generator output (-/+)
Negative frequency limit –
3
Ramp generator output
Ramp generator output – Posi-
4
tive frequency limit
Ramp generator output with
5
window
6
0 – Ramp generator output
Ramp generator output with
7
window and On/Off limits
For the selection of this parameter in NXS drives, see ID644.
1285 POSITIVE FREQUENCY LIMIT 6 (2.6.20)
Use this parameter to set the final frequency reference limit for the positive direction.
Maximum frequency limit for the drive. The parameter is available for NXP drives only.
1286 NEGATIVE FREQUENCY LIMIT 6 (2.6.19)
Use this parameter to set the final frequency reference limit for the negative direction.
Minimum frequency limit for the drive. The parameter is available for NXP drives only.
1287 MOTORING TORQUE LIMIT 6 (2.6.22)
Use this parameter to set the maximum torque limit of the motoring side.
LOCAL CONTACTS: HTTP://DRIVES.DANFOSS.COM/DANFOSS-DRIVES/LOCAL-CONTACTS/
VACON · 343