Wiring Periphery Module - YASKAWA VIPA System MICRO Manual

Table of Contents

Advertisement

VIPA System MICRO

2.5.2 Wiring periphery module

Periphery module con-
nector
Data
Wiring procedure
Insert wire
Remove wire
Fusing
HB400 | CPU | M13-CCF0000 | en | 18-50
For wiring the periphery module has removable connectors. With the wiring of the con-
nectors a "push-in" spring-clip technique is used. This allows a quick and easy connection
of your signal and supply lines. The clamping off takes place by means of a screwdriver.
U
240V AC / 30V DC
max
I
10A
max
Cross section
0.2 ... 1.5mm
Stripping length 10mm
Use for wiring rigid wires respectively use wire sleeves. When using stranded wires you
have to press the release button with a screwdriver during the wiring.
1
Labeling on the casing
2
Status LED
3
Release area
4
Connection hole for wire
5
Pin 1 of the connector is labelled by a white line
The wiring happens without a tool.
Determine according to the casing labelling the connection position and insert
through the round connection hole of the according contact your prepared wire until
it stops, so that it is fixed.
ð By pushing the contact spring opens, thus ensuring the necessary contact pres-
sure.
The wire is to be removed by means of a screwdriver with 2.5mm blade width.
1.
Press with your screwdriver vertically at the release button.
ð The contact spring releases the wire.
2.
Pull the wire from the round hole.
CAUTION!
The power section supply of the output modules DO16 is to be exter-
nally protected with a 10A fuse (fast) respectively by a line circuit
breaker 10A characteristics Z.
The power section supply of the output part of the DIO8 is to be
externally protected with a 5A fuse (fast) respectively by a line circuit
breaker 5A characteristics Z.
2