VIPA System MICRO
HB400 | CPU | M13-CCF0000 | en | 18-50
Hardware configuration - Ethernet PG/OP channel > Take IP address parameters in project
The configuration happens according to the following procedure:
1.
Open the Siemens hardware configurator and, if not already done, configure the
Siemens CPU 314C-2 PN/DP (314-6EH04-0AB0 V3.3).
2.
Place for the Ethernet PG/OP channel at slot 4 the Siemens CP 343-1 (SIMATIC
300 \ CP 300 \ Industrial Ethernet \CP 343-1 \ 6GK7 343-1EX30 0XE0 V3.0).
CAUTION!
Please configure the diagnostic addresses of the CP343-1EX30 for
'PN-IO' , 'Port1' and 'Port2' so that no overlaps occur in the
periphery input area. Otherwise your CPU can not start-up and you
receive the diagnostic entry 0xE904. These addresses overlaps are
not recognized by the Siemens SIMATIC Manager.
3.
Open the Properties dialog by double-clicking on 'PN-IO' of the CP 343-1EX30 and
enter the previously assigned IP address data and a subnet for the CP at
'Properties' . The IP address data are not accepted without subnet assignment!
4.
Transfer your project.
1
Ethernet PG/OP channel
Deployment CPU M13-CCF0000
75