YASKAWA VIPA System MICRO Manual page 125

Table of Contents

Advertisement

VIPA System MICRO
Hardware interrupt
Overflow
Underflow
Max. frequency
Counting signals/HW gate
Latch
HB400 | CPU | M13-CCF0000 | en | 18-50
Description
Hardware interrupt overflow
n
enabled: Hardware interrupt on overflow the upper
counter limit
n
disabled: no hardware interrupt
Hardware interrupt on underrun
enabled: Hardware interrupt on underflow the lower
n
counter limit
n
disabled: no hardware interrupt
Description
Specify the max. frequency for track A/pulse,
track B/direction and HW gate
Frequency
shortest permissible count pulse
1kHz
400µs
2kHz
200µs
5kHz
80µs
10kHz
40µs
30kHz
13µs
60kHz
6.7µs
Specify the max. frequency for the latch signal
Frequency
shortest permissible Latch pulse
1kHz
400µs
2kHz
200µs
5kHz
80µs
10kHz
40µs
30kHz
13µs
60kHz
6.7µs
Deployment I/O periphery
Counting > Parametrization
Assignment
disabled
disabled
Assignment
60kHz
10kHz
125