VIPA System MICRO
Fusing
Remove connector
HB400 | CPU | M13-CCF0000 | en | 18-50
(1) X2: 4L+: DC 24V power section supply for integrated outputs
X1: 3L+: DC 24V power section supply for integrated inputs
(2) X6: 1L+ DC 24V for electronic power supply
The electronic power section supply is internally protected against higher
voltage by fuse. The fuse is located inside the CPU and can not be
changed by the user.
CAUTION!
The power section supply of the internal DOs is to be externally pro-
tected with a 8A fuse (fast) respectively by a line circuit breaker 8A
characteristics Z.
By means of a screwdriver there is the possibility to remove the connectors e.g. for
module exchange with a fix wiring. For this each connector has indentations for unlocking
at the top. Unlocking takes place by the following proceeding:
1.
Remove connector:
Insert your screwdriver from above into one of the indentations.
Basics and mounting