Frequency Measurement; Properties - YASKAWA VIPA System MICRO Manual

Table of Contents

Advertisement

Deployment I/O periphery
Frequency measurement > Properties

5.7 Frequency measurement

5.7.1 Properties

Measuring procedure
140
n
In this operating mode the CPU counts the incoming pulses during a specified inte-
gration time and outputs them as frequency value.
n
Integration time 10ms ... 10000ms in steps of 1ms configurable
Control by the user program via SFB 48
n
More information about the usage of this block may be found in the
manual "SPEED7 Operation List" from VIPA.
1
Integration time
2
Counting pulse
3
SW gate
4
Frequency measurement start
5
Frequency measurement stop
The measurement is carried out during the integration time and is updated after the
n
integration time has expired.
n
If the period of the measured frequency exceeds the assigned integration time, this
means there was no edge 0-1 during the measurement, the measurement value 0 is
returned.
n
The calculated frequency value is supplied in "mHz" units.
n
The measurement value can be read with MEAS_VAL from SFB 48.
n
As long as the SW gate is open, you can request the calculated frequency.
n
The number of activated channels does not influence the max. frequency, which is
defined in the technical data.
1
Integration time
2
Counting pulse
3
SW gate
4
Evaluated frequency
The counting function is disabled during the pulse width modulation on
the same channel.
VIPA System MICRO
HB400 | CPU | M13-CCF0000 | en | 18-50

Advertisement

Table of Contents
loading

Table of Contents