Deployment CPU M13-CCF0000

CMD - auto commands

4.17
CMD - auto commands
Overview
Command file
Commands
Command
CMD_START
WAIT1SECOND
LOAD_PROJECT
SAVE_PROJECT
FACTORY_RESET
DIAGBUF
SET_NETWORK
CMD_END
WEBPAGE
WEBVISU_PGOP_ENABLE
102
A Command file at a memory card is automatically executed under the following condi-
tions:
n
CPU is in STOP and memory card is plugged
n
After each PowerON
The Command file is a text file, which consists of a command sequence to be stored as
vipa_cmd.mmc in the root directory of the memory card. The file has to be started by
CMD_START as 1. command, followed by the desired commands (no other text) and
must be finished by CMD_END as last command.
Text after the last command CMD_END e.g. comments is permissible, because this is
ignored. As soon as the command file is recognized and executed each action is stored
at the memory card in the log file logfile.txt. In addition for each executed command a
diagnostics entry may be found in the diagnostics buffer.
Please regard the command sequence is to be started with CMD_START and ended with
CMD_END.
Description
In the first line CMD_START is to be located.
There is a diagnostics entry if CMD_START is missing.
Waits about 1 second.
The function "Overall reset and reload from memory card"
is executed. The wld file located after the command is
loaded else "s7prog.wld" is loaded.
The recent project (blocks and hardware configuration) is
stored as "s7prog.wld" at the memory card. If the file just
exists it is renamed to "s7prog.old". If your CPU is pass-
word protected so you have to add this as parameter. Oth-
erwise there is no project written.
Example: SAVE_PROJECT password
Executes "factory reset".
The current diagnostics buffer of the CPU is stored as "dia-
gbuff.txt" at the memory card.
IP parameters for Ethernet PG/OP channel may be set by
means of this command. The IP parameters are to be
given in the order IP address, subnet mask and gateway in
the format x.x.x.x each separated by a comma. Enter the
IP address if there is no gateway used.
In the last line CMD_END is to be located.
Saves all information on the device web page (Expert-
View) as webpage.txt on the memory card
'Accessing the web server' page 85
Enable WebVisu project via Ethernet PG/OP channel
VIPA System MICRO
Diagnostics
entry
0xE801
0xE8FE
0xE803
0xE805
0xE806
0xE807
0xE80B
0xE80E
0xE802
0xE804
Ä Chap. 4.10
0xE82C
HB400 | CPU | M13-CCF0000 | en | 18-50