Wiring; Wiring Cpu - YASKAWA VIPA System MICRO Manual

Table of Contents

Advertisement

VIPA System MICRO

2.5 Wiring

2.5.1 Wiring CPU

CPU connector
Data
Wiring procedure
Insert wire
HB400 | CPU | M13-CCF0000 | en | 18-50
CAUTION!
Consider temperature for external cables!
Cables may experience temperature increase due to system heat dissi-
pation. Thus the cabling specification must be chosen 5°C above ambient
temperature!
CAUTION!
Separate insulation areas!
The system is specified for SELV/PELV environment. Devices, which are
attached to the system must meet theses specifications. Installation and
cable routing other than SELV/PELV specification must be separated
from the system's equipment!
For wiring the CPU has removable connectors. With the wiring of the connectors a "push-
in" spring-clip technique is used. This allows a quick and easy connection of your signal
and supply lines. The clamping off takes place by means of a screwdriver.
U
30V DC
max
I
10A
max
Cross section
0.2 ... 1.5mm
Stripping length 10mm
Use for wiring rigid wires respectively use wire sleeves. When using stranded wires you
have to press the release button with a screwdriver during the wiring.
1
Labeling on the casing
2
Status LED
3
Release area
4
Connection hole for wire
5
Pin 1 of the connector is labelled by a white line
The wiring happens without a tool.
Determine according to the casing labelling the connection position and insert
through the round connection hole of the according contact your prepared wire until
it stops, so that it is fixed.
ð By pushing the contact spring opens, thus ensuring the necessary contact pres-
sure.
2
(AWG 24 ... 16)
Basics and mounting
Wiring > Wiring CPU
19