5.1 I/O Module Setting

I/O Module Setting
To use the JANCD-YEW01-E board on the DX200, the I/O module must
be set according to the following procedure.
Check to be sure that the power supply of the DX200 is turned OFF.
Then, install the JANCD-YEW01-E board all of whose switches are
properly set to the inside of the DX200 cabinet. When installing the board,
refer to chapter 4 "Board Installation" .
When setting the I/O module, set the security mode to the
management mode.
SUPPLE-
When the security mode is set either to the operation mode
MENT
or the editing mode, only the setting status can be referred
to.
1. Press and hold [MAIN MENU], and turn ON the power.
– The Main Menu is displays.
2. Select the {SYSTEM} under the Main Menu.
3. Set the security mode to the "Management Mode".